Operation, Maintenance and Repair of Auxiliary Generators by Department of the Army and the Navy - HTML preview

PLEASE NOTE: This is an HTML preview only and some elements such as links or page numbers may be incorrect.
Download the book in PDF, ePub, Kindle for a complete version.

powered to be put in a position where stored energy

and status of electric power.

can be released to close or open the contacts very

e. Protects the generation and distribution sys-

quickly. Closing or tripping action is applied man-

tems.

ually (by hand or foot power) or electrically (where

a solenoid provides mechanical force). The me-

5-2. Types of switchgear.

chanical force may be applied magnetically. Air

Voltage classification. Low voltage and medium

circuit breakers contain power sensor overcurrent

voltage switchgear equipment are used in auxiliary

trip devices that detect an overcurrent to the load

power generation systems. Switchgear at military

and initiate tripping or opening of the circuit

installations is usually in a grounded, metal enclo-

breaker.

sure (see fig 5-l). Per the Institute of Electrical and

(a) Manual circuit breakers employ spring-

Electronics Engineers (IEEE), equipment rated up

operated, stored-energy mechanisms for operation.

to 1000 volts AC is classed as low voltage. Equip-

Release of the energy results in quick operation of

ment equal to or greater than 1000 volts but less

the mechanism to open or close the contacts. Oper-

than 100,000 volts AC is classed as medium voltage.

ating speed is not dependent on the speed or force

a. Low voltage. Major elements of low voltage used by the operator to store the energy.

switchgear are circuit breakers, potential trans-

(b) Fast and positive action prevents unnec-

formers, current transformers, and control circuits,

essary arcing between the movable and stationary

refer to paragraph 5-3. Related elements of the

contacts. This results in longer contact and breaker

switchgear include the service entrance conductor,

life.

main box, switches, indicator lights, and instru-

(c) Manual stored-energy circuit breakers

ments . The service entrance conductor and main

have springs which are charged (refer to the glos-

bus (sized as required) are typical heavy duty con-

sary) by operation of the insulated handle. The

ductors used to carry heavy current loads.

charging action energizes the spring prior to closing

b. Medium voltage. Medium voltage switchgear

or opening of the circuit breaker. The spring, when

consists of major and related elements as in low

fully charged, contains enough stored energy to pro-

voltage switchgear. Refer to paragraph 5-4 for de-

vide at least one closing and one opening of the

tails. Construction of circuit breakers employed in

circuit breaker. The charged spring provides quick

the two types of switchgear and the methods to

and positive operation of the circuit breaker. Part of

accomplish breaker tripping are the primary differ-

the stored energy, which is released during closing,

ences. The service entrance conductors and main

may be used to charge the opening springs.

5-1

TM 5-685/NAVFAC MO-912

Figure 5-l. Typical arrangement of metal enclosed switchgear.

(d) Some manual breakers require several

ate. Arcing and intermediate contacts are adjusted

up-down strokes to fully charge. The springs are

to open after the main contacts open to reduce burn-

released on the final downward stroke. In either of

ing or pitting of the main contacts.

the manual units, there is no motion of the contacts

(i) A typical power sensor for an air circuit

until the springs are released.

breaker precisely controls the breaker opening time

(e) Electrical quick-make/quick-break break-

in response to a specified level of fault current. Most

ers are operated by a motor or solenoid. In small

units function as overcurrent trip devices and con-

units, a solenoid is used to conserve space. In large

sist of a solenoid tripper and solid-state compo-

sizes, an AC/DC motor is used to keep control-power

nents. The solid-state components are part of the

requirements low (4 amps at 230 volts).

power sensor and provide precise and sensitive trip

(f) When the solenoid is energized, the sole-

signals.

noid charges the closing springs and drives the

(2) Molded-case circuit breakers. Low current

mechanism past the central/neutral point in one

and low energy power circuits are usually controlled

continuous motion. Motor-operated mechanisms au-

by molded-case circuit breakers. The trip elements

tomatically charge the closing springs to a predeter-

act directly to release the breaker latch when the

mined level. When a signal to close is delivered, the

current exceeds the calibrated current magnitude.

springs are released and the breaker contacts are

Typical time-current characteristic curves for

closed. The motor or solenoid does not aid in the

molded-case circuit breakers are shown in figure

closing stroke; the springs supply all the closing

5-3.

power. There is sufficient stored-energy to close the

(a) Thermal-magnetic circuit breakers have

contacts under short-circuit conditions. Energy for

a thermal bi-metallic element for an inverse time-

opening the contacts is stored during the closing

current relationship to protect against sustained

action.

overloads. This type also has an instantaneous mag-

(g) A second set of springs opens the contacts

netic trip element for short-circuit protection.

when the breaker receives a trip impulse or signal.

(b) Magnetic trip-only circuit breakers have

The breaker can be operated manually for mainte-

no thermal elements. This type has a magnetic trip-

nance by a detachable handle.

ping arrangement to trip instantaneously, with no

(h) Circuit breakers usually have two or

purposely introduced time delay, at currents equal

three sets of contacts: main; arcing; and intermedi-

to, or above, the trip setting. These are used only for

5-2

TM 5-685/NAVFAC MO-912

4 5 0 V O L T S , 3 P H 6 0 C P S

GENERATOR BUS

LEGEND

- AMMETER

-

V R

VOLTAGE REGULATOR

- WATTMETER

- SYNCHROSCOPE

VM

VOLTMETER

TEMPERATURE METER

P T

POTENTIAL TRANSFORMER

GEN. CKT BREAKER

C T

CURRENT TRANSFORMER

GE. CKT BREAKER

F U S E

GOVERNOR

Figure 5-2. Typical switchgear control circuitry, one-line diagram.

short-circuit protection of motor branch circuits (1) Ratings. A PT is rated for the primary volt-where motor overload or running protection is pro- age along with the turns (step down) ratio to secure vided by other elements. 120 VAC across the secondary.

(c) Non-automatic circuit interrupters have

(2) Application. The primary of potential trans-

no automatic overload or short circuit trip elements.

formers is connected either line-to-line or line-to-

These are used for manual switching and isolation.

neutral, and the current that flows through this

Other devices must be provided for short circuit and

winding produces a flux in the core. Since the core

overload protection.

links the primary and secondary windings, a volt-

b. Potential transformers. A potential trans-

age is induced in the secondary circuit (see fig 5-4).

former (PT) is an accurately wound, low voltage loss

The ratio of primary to secondary voltage is in pro-

instrument transformer having a fixed primary to

portion to the number of turns in the primary and

secondary “step down” voltage ratio. The PT is

secondary windings. This proportion produces 120

mounted in the high voltage enclosure and only the

volts at the secondary terminals when rated voltage

low voltage leads from the secondary winding are

is applied to the primary.

brought out to the metering and control panel. The

(3) Dot convention. A dot convention is used in

PT isolates the high voltage primary from the me-

figure 5-5. The dot convention makes use of a large

tering and control panel and from personnel. The

dot placed at one end of each of the two coils which

step down ratio produces about 120 VAC across the

are mutually coupled. A current entering the dotted

secondary when rated voltage is applied to the pri-

terminal of one coil produces an open-circuit voltage

mary. This permits the use of standard low voltage

between the terminals of the second coil. The volt-

meters (120 VAC full scale) for all high voltage cir-

age measured with a positive voltage reference at

cuit metering and control.

the dotted terminal of the second coil.

5-3

TM 5-685/NAVFAC MO-912

CURRENT IN AMPERES AT-

a

0 7

0 6

0 1

CURRENT IN AMPERES AT 13.8K VOLTS

Figure 5-3. Typical time-current characteristic curve.

c. Current transformers. A current transformer

either a toroid (doughnut) winding with a primary

(CT) is an instrument transformer having low

conductor wire passing through the “hole”, or a sec-

losses whose purpose is to provide a f’ixed primary

tion of bus bar (primary) around which is wound the

to secondary step down current ratio. The primary

secondary. The bus bar CT is inserted into the bus

to secondary current ratio is in inverse proportion to

being measured. The CT ratio is selected to result in

the primary to secondary turns ratio. The secondary

a five ampere secondary current when primary

winding thus has multiple turns. The CT is usually

rated current is flowing (see fig 5-4).

5 - 4

TM 5-685/NAVFAC MO-912

POTENT I AL CURRENT

TRANSFORMER TRANSFORMER

L I

D

V - V O L T M E T E R W-WATTMETER A-AMMETER

Figure 5-4. Instrument transformers, typical applications.

(1) Ratings. Toroidal CTs are rated for the size

cuit. Never open a CT secondary while the primary

of the primary conductor diameter to be surrounded

circuit is energized.

and the primary to secondary current (5A) ratio.

d. Polarities. When connection secondaries of PTs

Bus bar type CTs are rated for the size of bus bar,

and Cts to metering circuits the correct polarities of

primary voltage and the primary to secondary cur-

all leads and connections must be in accordance

rent 5A) ratio.

with the metering circuit design and the devices

(2) Application. The primary of a CT is either

connected. Wrong polarity connections will give

the line conductor or a section of the line bus. The

false readings and result in inaccurate data, dam-

secondary current, up to 5A, is directly proportional

age and injury. All conductors and terminations

to the line current. The ratio of the primary to

should carry identification that matches schemat-

secondary current is inversely proportional to the

ics, diagrams and plans used for construction and

ratio of the primary turns to secondary turns.

maintenance.

(3) Safety. A CT, in stepping down the current,

e. Control circuits. Switchgear control circuits also steps up voltage. The voltage across the second-provide control power for the starting circuit of the

ary is at a dangerously high level when the primary

prime movers and the closing and tripping of the

is energized. The secondary of a CT must either be

switchgear circuit breakers. Additionally, the con-

shorted or connected into the closed metering cir-

trol circuits provide control power to operate the

5-5

TM 5-685/NAVFAC MO-912

various relays and indicating lights associated with

the control circuitry. The control circuits are classi-

fied as either AC or DC.

(1) AC control circuits. AC control circuits usu-

_

PRIMARY

ally derive their power from the source side of the

circuit breaker being controlled. This procedure ap-

plies to main incoming line circuit breakers, genera-

tor circuit breakers, and feeder circuit breakers (see

fig 5-6). Depending on the system voltage, the con-

trol power can be taken directly from the main bus

since it can be connected through a control power

transformer.

(2) Tie break er control circuits. In systems us-

ing a tie breaker, the control power for the tie

breaker and the feeder breakers is supplied through

a throw-over scheme so control power is available if

either side of the tie breaker is energized (see fig

5-7). In applications that require synchronizing cir-

cuitry, the running and incoming control buses are

usually supplied via the potential transformers. The

transformer primaries are connected to both the

Figure 5-5. Current flow in instrument transformers. ‘Polarity”

line side and the load side of the circuit breakers

marks show instantaneous flows.

that are used for synchronizing. The transformer

M A I N I N C O M I N G L I N E GENERATOR

CONTROL

POWER

TRANSFORMER

F U S E CONTROL POWER

TRANSFORMER

M A I N

CONTROL

POWER

GE N E R A T O R

BUS

B R E A K E R I

F U S E ,

FEEDER

BREAKER

L O A D

LOAD

Figure 5-6. AC control circuits.

TM 5-685/NAVFAC MO-912

LOAD

Figure 5-7. AC control circuits with tie circuit breaker.

secondaries are connected to the proper control bus

program that is built around equipment and system

through contacts on the synchronizing switch, or

records and visual inspections. The program is de-

through contacts on certain auxiliary relays. The

scribed in the manufacturer’s literature furnished

synchronizing switch would be used for manual op-

with the components. If a problem develops, the

eration and the auxiliary relay would be used when

user should perform general troubleshooting proce-

automatic synchronizing is provided.

dures. The program includes appropriate analysis of

(3) DC control circuits. DC control circuits de-

the records.

rive their power from a battery source consisting of

(1) Record keeping. Equipment and system log

a bank of batteries and a battery charger that main-

sheets are important and necessary functions of

tains the batteries at the proper charge. The battery

record keeping. The log sheets must be specifically

bank can be rated at various levels ranging between

developed to suit individual application (i.e., auxil-

24 volts and 125 volts DC. Those circuits that re-

iary use).

quire a source of control power completely indepen-

(2) Troubleshoo ing

t

. Perform troubleshooting

dent of the power system are connected to the DC

procedures when abnormal operation of the system

control bus. Examples of these are the prime mover

or equipment is observed. Maintenance personnel

starting circuits, and in some cases, the trip circuits

must then refer to records for interpretation and

for the circuit breakers when devices, other than

comparison of performance data (i.e., log sheets).

the direct-acting overcurrent trip devices, are used.

Comparisons of operation should be made under

Also, the closing circuits for the circuit breakers are

equal or closely similar conditions of load and ambi-

sometimes connected to the DC control bus.

ent temperature. The general scheme for trouble-

f. Service practices. Service practices for low volt-shooting is outlined in the following paragraphs and

age switchgear consist of a complete maintenance

troubleshooting table.

5-7

TM 5-685/NAVFAC MO-912

(a) Use recognized industrial practices as the

several times during the period, preferably under

general guide for servicing and refer to manufactur-

load. If the breaker is operated by a relay or a

er’s literature.

switch, it should be so operated at this time.

(b) The user should refer to manufacturer’s

( e ) Service for molded-case circuit breakers

literature for specific information on individual cir-

consists of the following procedures. Inspect connec-

cuit breakers.

tions for signs of arcing or overheating. Replace

(c) General service information for circuit

faulty connectors and tighten all connections. Clean

breakers includes the following safety require-

the connecting surfaces. Perform overload tripping

ments. Do not work on an energized breaker. Do not

tests. Verify automatic opening of breaker. Verify

work on any part of a breaker with test couplers

that the magnetic tripping feature is operating. Per-

engaged. Test couplers connect the breaker to the

form circuit breaker overload tripping tests. Proper

control circuit during testing. Spring-charged

action of the breaker tripping components is veri-

breaker mechanisms shall be serviced only by per-

fied by selecting a percentage of breaker current

sonnel experienced in releasing the spring load in a

rating (such as 300%) for testing. This overload is

controlled manner. Make operational tests and

applied separately to each pole of the breaker to

checks on a breaker after maintenance, before it is

determine how it will affect automatic opening of

returned to service. Do not work on a spring-

the breaker. Refer to manufacturer’s test informa-

charged circuit breaker when it is in the charged

tion. Turn the breaker on and off several times to

position.

verify satisfactory mechanical operation.

(d) Switchgear needs exercise. If the circuit

( f ) Service for air circuit breakers consists of

breaker remains idle, either open or closed, for six

the following procedure (see fig 5-8). Install the

months or more, it should be opened and closed

safety pin to restrain the closing spring force. With

CONNECTED

ALL POWER

(PR I MA R Y

CONTROL)

CONTROL POWER

STILL CONNECTED

--DISCONNECTED

ALL POWER DISCON-

NECTED

WITHDRAWN

BREAKER WITHDRAWN

READY FOR REMOVAL

Figure 5-8. Maintenance for typical low voltage switchgear with air circuit breakers.

5-8

TM 5-685/NAVFAC MO-912

the pin in place, the contacts will close slowly when

Table 5-l. Low voltage circuit breaker

the breaker is manually operated. Inspect connec-

troubleshooting-Continued

tions for signs of arcing or overheating. Replace

Note

faulty connectors and tighten all connections. Clean

the connecting surfaces. An infrared (IR) survey is a

Refer to manufacturer’s literature for specific information on recommended inspection procedure. The IR survey

individual circuit breakers.

should be performed when the circuit breaker is

Cause

Remedy

under load and closed to detect overheating of con-

FALSE TRIPPING

nections. Perform general troubleshooting of the

Overcurrent pick-up too low

Check application of overcurrent

breaker (refer to the following table) if a problem

trip device

develops. If the trouble cannot be corrected, refer to

Check application of overcurrent

the manufacturer’s literature for specific informa-

Overcurrent time setting too short

trip device

tion on individual breakers. Instrument transform-

ers require no care other than keeping them dry

Mechanical binding in over-

Correct binding or replace over-

current trip device

and clean. Refer to manufacturer’s literature if spe-

condition current trip device

cific information is required. Information related to

Captive thumbscrew on power sen-

Adjust power sensor. Tighten

control circuit components is provided in paragraph

sor loose. Fail safe circuitry reverts

thumbscrew on desired setting

characteristics to minimum setting

5-3 e of this chapter.

and maximum time delay

Ground sensor coil improperly con- Check polarity of connections to nec ted

coil. Check continuity of shield

Table 5-l. Low voltage circuit breaker troubleshooting.

and conductors connecting the ex-

ternal ground sensor coil

Note

FAILURE TO CLOSE AND LATCH

Refer to manufacturer’s literature for specific information on Binding in attachments preventing Realign and adjust attachments individual circuit breakers.

resetting of latch

Cause Remedy

Latch out of adjustment

Adjust latch

OVERHEATING